ED41, Overload - External brake resistor
The load of the external brake resistor has reached a critical value.
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
---|---|
ED41 |
60737 |
Class |
Type |
---|---|
Warning |
Warning / Information |
Standard Reaction |
Reset |
---|---|
No |
Warning: No reset required. |
Possible Causes |
Solutions |
---|---|
The external brake resistor is just below the overload limit. If the limit value is exceeded, the brake resistor will be turned off and the internal ballast power will be lost. |
|
![]() | Please consider this note! If you ignore this warning and the load of the external brake resistor continues to increase, it will be turned off and the voltage in the DC link can continue to increase, to the point where the servo driver turns off with error "FD4F". |