Disassembly
| |
Serious injuries due to premature disconnection from the There is still a life-threatening voltage of > 848 V DC on the capacitors after disconnection from the supply network. Serious or even fatal injuries may result if this is ignored.
|
|
AX8000 series |
Discharge time [min] |
|---|---|
|
AX8108, AX8118, AX8128 |
30 |
|
AX8206 |
30 |
|
AX8525, AX8540 |
30 |
|
AX8600 |
30 |
|
AX8620, AX8640 |
30 |
|
AX8820 |
30 |
|
AX8831, AX8832 |
30 |
|
AX5000 series |
Discharge time [min] |
|---|---|
|
AX5101 to AX5125 |
5 |
|
AX5201, AX5203, AX5206 |
5 |
|
AX5140, AX5160, AX5172 |
15 |
|
AX5190, AX5191 |
30 |
|
AX5192, AX5193 |
45 |
|
AMP8000 series |
Discharge time [min] |
|---|---|
|
AMP8620-2005-0xxx |
30 |
|
AMP8805-10x0-0000 |
30 |
![]() | Do not remove components from the products Only Contact Beckhoff Service for further information. |
Removing the braking resistor from the machine
- ►Remove cables and electrical connections
- ►Loosen and remove the braking resistor fixing screws
- ►Transport the braking resistor to the workplace or put it into storage