Electrical installation

WARNING

Serious injuries due to premature disconnection from the
supply network

There is still a life-threatening voltage of > 848 V DC on the capacitors after disconnection from the supply network. Serious or even fatal injuries may result if this is ignored.

  • Keep to the waiting times after disconnection from the supply network

AX8000 series

Discharge time [min]

AX8108, AX8118, AX8128

30

AX8206

30

AX8525, AX8540

30

AX8600

30

AX8620, AX8640

30

AX8820

30

AX8831, AX8832

30

AX5000 series

Discharge time [min]

AX5101 to AX5125

5

AX5201, AX5203, AX5206

5

AX5140, AX5160, AX5172

15

AX5190, AX5191

30

AX5192, AX5193

45

AMP8000 series

Discharge time [min]

AMP8620-2005-0xxx

30

AMP8805-10x0-0000

30

 

Notice

Damage due to improper grounding and faulty contacting

Improper grounding or faulty contacting can lead to damage to the multi-axis servo system or to EMC interference emissions.

  • Establish a conductive connection of all components
  • The minimum cross-sections of separate protective conductors can be found in EN 61439-1
  • Only use shielded cables
  • Ground the shields of the ready-made cables via the mounting plate and place the star point centrally on the unpainted mounting plate
  • For larger applications, implement the potential equalization via PE rails

Electrical installation 1:
Fit single wires [1] with ferrules
Wire the cores according to the specifications in the technical data.