During operation

Observe the discharge times of the capacitors

Observe the following delay times after disconnecting from the supply network:

AX8000 series

Discharge time [min]

AX8108, AX8118, AX8128

30

AX8206

30

AX8525, AX8540

30

AX8600

30

AX8620, AX8640

30

AX8820

30

AX8831, AX8832

30

AX5000 series

Discharge time [min]

AX5101 to AX5125

5

AX5201, AX5203, AX5206

5

AX5140, AX5160, AX5172

15

AX5190, AX5191

30

AX5192, AX5193

45

AMP8000 series

Discharge time [min]

AMP8620-2005-0xxx

30

AMP8805-10x0-0000

30

 

Do not work on live electrical parts

Do not open the multi-axis servo system while it is live. Measure the voltage on the DC link test contacts DC+ und DC-. Only work on the multi-axis servo system when the voltage has dropped to < 50 V. Ensure that the protective conductor is connected properly. Never loosen electrical connections when live. Disconnect all components from the mains and secure them against being switched on again.

Do not touch hot surfaces

Check the temperature of the surfaces with a thermometer. Do not touch the components during and immediately after operation. Allow the components to cool sufficiently after switching off.

Avoid overheating

Operate the components according to the technical specifications. Refer here to the chapter Technical data. Provide for sufficient cooling. Switch the components off immediately if the temperature is too high.