Data for operation and environment

Notice

Reduced service life due to improper operation

Short-term or long-term operation outside of the specifications listed here may reduce the service life of the Braking resistors.

  • Operate the Braking resistors only under the operating and environmental conditions specified in this chapter

Beckhoff products are designed for operation under certain environmental conditions, which vary according to the product. The following specifications must be observed for operation and environment in order to achieve the optimum service life of the products.

Environmental requirements

Climate category – operation

3K3 according to EN 60721

Ambient temperature during operation

-15…+70°C
At temperatures above 40°C, the continuous power rating must be reduced by 4% for every 10 K increase in temperature

Ambient temperature during transport

-15…+70°C, maximum fluctuation 20 K/hour

Ambient temperature during storage

-15…+70°C, maximum fluctuation 20 K/hour

Power derating

No power derating up to 1,000 m above sea level

From 1,000 m up to a maximum of 4,000 m above sea level with a power derating

of 5%/1,000 m

Permissible humidity during operation

5% to 85% relative humidity, no condensation

Permissible humidity during transport and storage

5% to 85% relative humidity, no condensation

Corrosion protection

Strip-galvanized housing
Special measures are to be taken in consultation with the vendor if the environmental conditions are extreme or if they differ from those described in this chapter.

Pollution degree

According to EN 50124

Outdoor area: PD4
Indoor area: PD2

Specifications for intended use

Ventilation

Free convection

Insulation material class

N according to IEC 60085

Protection rating

Devices IP65

Installation position

Vertical or horizontal
according to chapter Installation position

Vibration resistance

Category 1 Class B according to DIN EN 61373

Shock resistance

Category 1 Class B according to DIN EN 61373

Approvals

cURus
See chapter: Directives and standards