AX2090-ND80-0020 to -0080

The mains chokes AX2090-ND80-0020 to -0080 are intended for operation with three-phase supplies of the AX8000 multi-axis servo system.

 

AX2090-ND80-0020 to -0080 1:

Installation position

The standard installation position of the mains choke is the vertical, upright installation position. Alternatively, wall mounting is possible as shown.

AX2090-ND80-0020 to -0080 2:

Clearances

The required minimum distance to neighboring parts must be maintained in order not to impede cooling. All figures in millimeters.

Mounting sequence

►Position the mains choke on the mounting surface.
►Mark the positions of the tapped holes on the mounting surface.
►Center and drill the thread holes.
►Cut the threads in the holes.
►Secure the mains choke on the mounting surface with suitable screws.
AX2090-ND80-0020 to -0080 3:

Connection

The mains chokes of the AX2090-ND80-xxxx series may only be operated at the corresponding terminal points of the AX8000 power supply modules:

 

Order of connection

►Connect the protective conductor connection of the mains choke to the PE bar
►Connect the mains choke to the corresponding terminals of the drive device
►Connect the mains choke to the supply network
AX2090-ND80-0020 to -0080 4:
AX2090-ND80-0020 to -0080 5:

Connecting the protective conductor connection

►Loosen screw [1] at the PE connection point
►Connect the pre-assembled PE cable to the connection point
►Insert screw [1] at the PE connection point and tighten with torque
AX2090-ND80-0020 to -0080 6:

Connecting the drive device

►Connect connection point L3/N to W2 [1].
►Connect connection point L2 to V2 [2]
►Connect connection point L1 to U2 [3].

Connecting the mains connection

►Connect phase L3 to W1 [1]
►Connect phase L2 to V1 [2]
►Connect phase L1 to U1 [3].