AX2090-ND80-0010

The AX2090-ND80-0010 mains choke is intended for operation with the AX8620 single-phase supply of the AX8000 multi-axis servo system.

 

AX2090-ND80-0010 1:

Installation position

The standard installation position of the mains choke is the vertical, upright installation position. Alternatively, wall mounting is possible as shown.

 

AX2090-ND80-0010 2:

Clearances

The required minimum distance to neighboring parts must be maintained in order not to impede cooling. All figures in millimeters.

Mounting sequence

►Position the mains choke on the mounting surface.
►Mark the positions of the tapped holes on the mounting surface.
►Center and drill the thread holes.
►Cut the threads in the holes.
►Secure the mains choke on the mounting surface with suitable screws.

 

AX2090-ND80-0010 3:

Connection

The mains choke AX2090-ND80-0010 may only be operated on contacts L1 and L3/N of slot X01 of the AX8620 power supply module.

Order of connection

►Connect the protective conductor connection of the mains choke to the PE bar
►Connect the mains choke to the corresponding terminals of the drive device
►Connect the mains choke to the supply network

Mains connection

AX2090-ND80-0010 4:
AX2090-ND80-0010 5:

Connecting the protective conductor

►Connect the pre-assembled PE cable to the flat connector [1] of the mains choke.

Connecting the drive device

►Connect connection point L1 of the servo drive to connection 1.2 [3] of the mains choke.
►Connect connection point L3/N of the servo drive to the neutral conductor of the supply network.

Connecting the supply network

►Connect phase L1 to connection 1.1 [3] of the mains choke.