Temperature switch
The temperature switch is exclusively used for temperature monitoring. The brake resistor is not switched off.
The temperature switch has a potential-free N/C contact, which enables immediate response to any overload of the brake resistor through analysis in the AX5000 or the PLC. Connect the cable directly to a free input of plug "X06". Then parameterize it such that the AX5000 stops the motor(s) with an emergency ramp or the PLC reads and processes this input.
|
Type |
Switching temperature |
Switching current |
|---|---|---|
|
[°C] |
[A] | |
|
AX2090-BW50-0300 |
180 |
2 |
|
AX2090-BW50-0600 |
180 |
2 |
|
AX2090-BW50-1600 |
180 |
2 |
|
AX2090-BW51-1000 |
180 |
2 |
|
AX2090-BW51-3000 |
85 |
2 |
|
AX2090-BW51-6000 |
85 |
2 |
|
AX2090-BW52-3000 |
85 |
2 |
|
AX2090-BW52-6000 |
85 |
2 |
|
AX2090-BW53-3000 |
85 |
2 |
|
AX2090-BW53-6000 |
85 |
2 |
|
AX2090-BW54-3000 |
85 |
2 |
|
AX2090-BW54-6000 |
85 |
2 |