Mounting positions and distances
(A) = vertical installation is only permitted according to the diagram (terminal box facing downwards).
(B) = horizontal installation
|
Assignment of the device classes | |
|---|---|
|
|
|
|
AX2090-BW50-xxxx AX2090-BW51-1000 |
AX2090-BW51-3000 and AX2090-BW51-6000 |
|
AX2090-BW52-3000 and AX2090-BW52-6000 | |
|
AX2090-BW53-3000 and AX2090-BW53-6000 | |
|
AX2090-BW54-3000 and AX2090-BW54-6000 | |
For all mounting positions the following minimum distances must be adhered to:
200 mm to adjacent components, walls etc. and 300 mm to components, ceilings etc. above. If the device is installed vertically (A), the minimum distance to components, floors etc. below is 200 mm in order to allow unobstructed flow of air to the brake resistor.

