Position of the extension card

EtherCAT AX2090-B110 extension card

The AX2090-B110 extension card is plugged and screwed into the servo drive's extension slot when the AX2000 is shipped.

Position of the plug

Position of the extension card 1:
Position of the extension card 2:

The AGND and DGND terminal points on plug X3 must be bridged!

Notice

Please note that the plug of the EtherCAT cable from the PC is plugged into socket X1 “IN” and that the signal from socket X2 “OUT” must be fed to socket X1 “IN” on the next AX2000 and so forth up to the last AX2000. If the sockets are mixed up, indefinable states and errors may occur.

Assembly

If the EtherCAT AX2090-B110 interface card has not yet been plugged into your servo drive, install it as follows: