Position of the extension card
EtherCAT AX2090-B110 extension card
The AX2090-B110 extension card is plugged and screwed into the servo drive's extension slot when the AX2000 is shipped.
Position of the plug


The AGND and DGND terminal points on plug X3 must be bridged!
Notice  | |
Please note that the plug of the EtherCAT cable from the PC is plugged into socket X1 “IN” and that the signal from socket X2 “OUT” must be fed to socket X1 “IN” on the next AX2000 and so forth up to the last AX2000. If the sockets are mixed up, indefinable states and errors may occur.  | 
Assembly
If the EtherCAT AX2090-B110 interface card has not yet been plugged into your servo drive, install it as follows:
- Lever out the cover of the option slot using a suitable screwdriver.
Make sure that no small parts (such as screws) fall into the open option slot! - Push the extension card carefully into the guide rails, making sure that it is not misaligned.
 - Push the extension card firmly down into the slot, until the front cover is level with the fixing plates.
This ensures that proper contact is made with the connectors. - Turn the screws in the front cover to tighten them in the threads of the fixing plates.