I/O connection X3

I/O connection X3 1:

The integrated ASI8100 stepper motor drive has a connector (M8 socket, 3-pin, A-coded) for integrated I/Os at slot X3. It is suitable for connecting end positions or external sensors and is designed as a fast digital input. It can be configured as a digital output via the CoE object 0x8030: DO Settings.

Signal/level X3 [Touch probe]

Contact

Function

Level/source

1

Output

24 V DC, 500 mA

3

GND

Externally connected

4

Input

1-wire connection, 24 V DC

Digital inputs (Touch probe)

Signal level high

≥ 5 V

Signal level low

≤ 2 V

Input current

5 … 6 mA

Pin assignment X3 [M8 socket, 3-pin, A-coded]

I/O connection X3 2:
Pinout X3

Contact

Function

Core color/
Core identification

1

Output

Brown

3

GND

Blue

4

Input

Black

The connection cables are not included in the scope of delivery. The wire colors apply to sensor cables from Beckhoff. For suitable connection cables, see sensor cable.

 

Display

Status LED

Slot X3 has a green LED labeled “IN”. It signals the status of the digital input. Slot X3 has a green LED labeled “OUT”. It signals the status of the digital output.

LED “IN”

Status display of digital input TP1

I/O connection X3 3:

LED

Meaning

Off

No control voltage present at the input, input inactive

Lit

Control voltage is present at the input, input active

LED “OUT”

Status display of digital output TP1

I/O connection X3 4:

LED

Meaning

Off

No control voltage at the output, output inactive

Lit

Control voltage is present at the output, output active