Power connection | X5
The load voltage UP supplies the motor and must be fed separately. If UP is switched off, the fieldbus function, the function of the inputs, and the supply of the sensors are maintained. The control voltage US supplies the fieldbus, the processor logic, and the digital I/Os and must be supplied separately.
Signals/levels X5 [supply]
Function | Level/source |
|---|---|
UP+ | +8…48 V DC |
UP- | GND |
US+ | +24 V DC |
US- | GND |
FE | (internally connected to the housing) |
The connection cables are not included in the scope of delivery. See power cables for suitable connection cables.