Power supply
The integrated stepper motor drive ASI8100 requires two supply voltages for operation:
- Control voltage US = 24 V DC
 - Peripheral voltage UP = 48 V DC (load voltage)
 
The voltages must be fed in at slot X5.
Notice  | |
Fuse protection of the load voltage The electrical fuse protection of the load voltage must be selected in such a way that the maximum current flowing is limited to 3 times the nominal current (max. 1 second)!  | 
Notice  | |
Malfunction due to equalizing currents on the protective conductor In the event of a fault, the resulting equalizing currents can lead to higher currents on the return conductors of the circuits and can damage them and/or the product. 
  |