Troubleshooting
The following table is to be seen as a “First Aid” box. There can be a large number of different reasons for a fault, depending on the particular conditions in your system. The fault causes described below are mostly those which directly influence the motor.
Our applications department can give you further help with your problems.
|
Error |
Possible cause |
Measures to remove the cause of the fault |
|---|---|---|
|
Motor doesn’t rotate |
Break in setpoint lead Motor phases in wrong sequence Drive is mechanically blocked |
Check setpoint lead Correct the phase sequence Check mechanism |
|
Motor runs away |
Motor phases in wrong sequence |
Correct the phase sequence |
|
Motor oscillates |
Break in the shielding of the feedback cable Amplification to high |
Replace the feedback cable Use motor default values |
|
Error message: output stage fault |
Motor cable has short circuit or earth leakage Motor has short circuit or earth leakage |
Replace motor cable Replace motor |
|
Error message: feedback |
Connector is not properly plugged in Break in cable, cable crushed or similar |
Check the plug connector Check cables |