Offset calculation
Carry out the wiring according to the arrangement of the coil units. You have to calculate the offset for the wiring. The offset indicates the number of coils by which the rotary field is shifted in the second coil unit.
Calculate the offset using the following equation: (PDM1M2/16) MOD 3
Information on PDM1M2 can be found in the chapter: Electrical connection
Information on wiring can be found in the chapter: Power supply
![]() | Example 1: AL8122 and AL8122 with cables in opposite directions PDM1M2 = 208 mm Offset = (208/16) MOD 3 = 1 Example 2: AL8122 and AL8122 with cables in opposite directions PDM1M2 = 192 mm Offset = (192/16) MOD 3 = 0 |