Connection to the cooling circuit
Notice | |
Damage due to faulty sealing Failure to observe the provisions for sealing the connections can result in damage to the motor and the entire system.
|
For the connection of the cooling hoses we recommend push-in fittings with male thread:
Coil unit | Male thread |
|---|---|
AL804x | M5 |
AL806x-1xxx | G 1/8 “ |
- ►Remove the plug [1] at the front of the coil unit
AL804x:
- ►Remove the plug on the opposite side of the coil unit
- ►Screw the threaded push-in fittings [2] into the holes provided
AL804x:
- ►Screw in the threaded push-in fittings on the opposite side of the coil unit
Notice | |
Shortened service life of the cooling hoses due to algae formation Algae can form in the cooling system if the wrong hoses are chosen. This can shorten the service life of the cooling hoses and reduce the performance of the motor.
|
For connecting the threaded push-in fittings, we recommend the following cooling hose sizes:
Coil unit | Hose | |
|---|---|---|
Inner diameter | Outer diameter | |
[mm] | ||
AL804x | 4 | 6 |
AL806x-1xxx | 6 | 8 |
- ►Insert the cooling hoses [3] into the threaded push-in fittings
AL804x:
- ►Connect cooling hoses at the opposite side of the coil unit