AL2xxx
Make sure that the minimum diameter for water flow is at least 2.5 mm, and that the internal diameter of the hose is at least 4 mm.
- Degrease the connector and the threaded holes. Allow the degreasing agent to evaporate completely before continuing.
- Place the plastic sealing ring on the connector.
- Apply a drop of Loctite 638/648 adhesive to the thread, and spread it all the way round.
- Attach the connector, and turn it until the sealing ring is visibly deformed. (This only requires a torque of 0.2 to 0.3 Nm!)
- Remove the excess adhesive.
- Let the adhesive harden for 4 hours before stressing it.
- Let the adhesive harden for about 12 hours before exposing it to pressure.
- The hoses must match the chosen connectors.
Water cooling connections that can be used for hoses with an inside diameter of 4 mm are, for example, the Festo PU-4 pneumatic or the very flexible PVC hose Rauclair E 4x1. Both hoses and connections can withstand a pressure of 2 bar.