3 x 400 V, 50 Hz
Rated input voltage UN= 3 x 400 V | Rated input frequency fN = 50 Hz
(1) | Power losses in % of the rated output certificate power | (0;25) | 2.09 | 2.13 | 1.48 | 1.59 | 1.17 | 1.23 | 1.20 |
(0;50) | 2.37 | 2.27 | 1.53 | 1.71 | 1.22 | 1.53 | 1.52 | ||
(0;100) | 2.65 | 2.63 | 1.97 | 2.31 | 1.81 | 1.92 | 2.22 | ||
(50;25) | 2.42 | 2.43 | 1.85 | 2.04 | 1.35 | 1.73 | 1.61 | ||
(50;50) | 1.54 | 2.62 | 1.88 | 2.24 | 1.71 | 1.62 | 2.02 | ||
(50;100) | 3.06 | 2.84 | 2.44 | 2.89 | 2.4 | 2.6 | 2.84 | ||
(90;50) | 2.67 | 2.81 | 1.41 | 2.52 | 1.73 | 2.08 | 2.41 | ||
(90;100) | 2.59 | 2.84 | 2.88 | 2.95 | 2.14 | 2.84 | 2.84 | ||
Losses in standby mode | % | 0.57 | 0.62 | 0.3 | 0.37 | 0.14 | 0.28 | 0.14 | |
W | 9.9 | 10.7 | 9 | 10.9 | 7.5 | 12 | 12 | ||
(2) | Efficiency level |
| IE2 | IE2 | IE2 | IE2 | IE2 | IE2 | IE2 |
(3) | Vendor name | Beckhoff Automation GmbH & Co. KG Hülshorstweg 20 33415 Verl Germany | |||||||
| Commercial register number | Gütersloh HRA 7075 | |||||||
(4) | Model identifier |
| AF1107 -3x00 | AF1207 -3x00 | AF1115 -3x00 | AF1215 -3x00 | AF1130 -3x00 | AF1222 -3x00 | AF1155 -3x00 |
(5) | Output apparent power | kVA | 1.32 | 1.34 | 2.55 | 2.67 | 4.94 | 3.87 | 7.82 |
(6) | Indicative rated output power PN | kW | 750 | 750 | 1500 | 1500 | 3000 | 2200 | 5500 |
(7) | Rated output current | A | 2.5 | 2.5 | 4.3 | 4.3 | 7.6 | 6 | 12.5 |
(8) | Maximum operating temperature | °C | 55 | ||||||
(9) | Rated input frequency | Hz | 50 | ||||||
(10) | Rated input voltage | V | 3 x 208 V AC-15% … 480 V AC+8% | ||||||
| Switching frequency | kHz | 4 | 4 | 4 | 4 | 4 | 4 | 4 |