Electromagnetic interference emission
The products described in the present manual meet the EMC requirements as per IEC 61800-3 if the EMC measures described in the present manual are implemented.
| |
ELECTROMAGNETIC DISTURBANCES OF SIGNALS AND DEVICES Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
These types of devices are not intended to be used on a low-voltage public network which supplies domestic premises. Radio frequency interference is expected if used in such a network.
| |
RADIO INTERFERENCE Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
EMC categories with external mains filter
For the economy variable frequency drive AF1000, the following categories for emission as per IEC 61800-3 are reached with a motor cable length ≤25 m if the EMC measures described in the present manual are implemented and if the external mains filters offered as accessories are used.
Emission type | Category |
|---|---|
Conducted emission | Category C2 |
Radiated emission | Category C3 |
Motor cable length ≤25 m
External mains filters as sum filters
Several devices can be connected to a common external mains filter.
The following mains filters are available for this purpose:
- AX2090-NF12-1020
- AX2090-NF12-3020
Prerequisites:
- Single-phase devices may only be connected to single-phase mains filters; three-phase devices may only be connected to three-phase devices.
- The total input current of the connected devices must be smaller than or equal to the permissible rated current of the mains filter.