Environmental conditions
Environmental requirements  | |
|---|---|
Climate category – operation  | 2K3 according to EN 60721  | 
Ambient temperature during operation  | +5 °C ... +40 °C, extended temperature range  | 
Ambient temperature during transport  | -25 °C ... +70 °C, maximum fluctuation 20 K/hour  | 
Ambient temperature during storage  | -25 °C ... +55 °C, maximum fluctuation 20 K/hour  | 
Power derating  | No power derating for installation altitudes of 1000 m above sea level with temperature reduction of 10 K/1000 m.  | 
Permissible humidity in operation  | 95 % relative humidity, no condensation  | 
Permissible humidity during transport and storage  | 5 % to 95 % relative humidity, no condensation  | 
Derating [%] at installation altitudes above 1000 m and 40°C  | |
|---|---|
2000 m above sea level  | 6  | 
3000 m above sea level  | 17  | 
4000 m above sea level  | 30  | 
5000 m above sea level  | 55  |