Transport
| |
Serious to fatal accidents caused by suspended loads A falling electric cylinder can cause serious to fatal accidents.
|
Notice | |
Damage to the electric cylinder Falling down and hard impacts will damage the electric cylinder.
|
Notice | |
Faults and damage to the electric cylinder If the electric cylinder is lifted on the shaft, this will cause faults and damage to the spindle drive.
|
Notice | |
Possible injuries and damage to the product Do not transport the electric cylinder with the spindle vertically downwards, as the spindle may come loose accidentally.
|
![]() | Legal regulations for the lifting of loads When transporting electric cylinders, comply with the legal regulations on lifting loads for employees. |
Operating equipment for flange fastening
Size | AA3023 | AA3033 | AA3053 |
---|---|---|---|
Hexagon socket head cap screw DIN EN ISO 4762–8.8 | M6 | M8 | M10 |
A-flange screw depth [mm] | 10 | 30 | 40 |
B-flange screw depth [mm] | 20 | 25 | 25 |
Tightening torque [Nm] | 10 | 24 | 50 |
The mounting holes on the A-flange and B-flange are suitable for fastening eyebolts for transport.