ST_LON_SNVT_environment

Genutzt durch: SNVT_environment

TYPE ST_LON_SNVT_environment :
STRUCT
  uiLampCurrent   : UINT;
  uiLampVoltage   : UINT;
  uiSupplyVoltage : UINT;
  uiSupplyCurrent : UINT;
  rBallastTemp    : REAL;
  rPower          : REAL;
  rPowerFactor    : REAL;
  udiRunHours     : UDINT;
  lrEnergy        : LREAL;
END_STRUCT
END_TYPE

uiLampCurrent: Min: 0 / Max: 65534 / Invalid: 65535 / Lamp current (milliAmperes). This is the current the lamp consumes.

uiLampVoltage: Min: 0 / Max: 65535/ Lamp Voltage (Volts). This is the lamp voltage.

uiSupplyVoltage: Min: 0 / Max: 65535 / Supply Voltage (Volts). This is the luminaire supply voltage.

uiSupplyCurrent: Min: 0 / Max: 65534 / Invalid: 65535 / Supply Current (milliAmperes). This is the luminaire supply current.

rBallastTemp: Min: -273.17 / Max: 327.67 / Ballast temperature (degrees Celsius). This is the temperature at the ballast.

rPower: Min: 0 / Max: 6553.5 / Power (Watts). The value shows the at this moment consumed power of the ballast and the luminaire.

rPowerFactor: Min: -1 / Max: 1 / Power factor. This is the luminaire power-factor.

udiRunHours: Min: 0 / Max: 4294967294 / Run Hours (hours). This are the run hours since the last maintenance.

lrEnergy: Min: -214748364.8 / Max: 214748364.7 / Energy (kiloWatt-hours). This is the energy the luminair has consumt since the last maintenance.

Voraussetzungen

Entwicklungsumgebung

Einzubindende TwinCAT 3 SPS-Bibliothek

TwinCAT ab v3.1.4020.14

Tc2_LON ab 3.3.4.0