80E0:12 Watchdog State
Output state after watchdog error. When the module loses communication to the EtherCAT master, the relay output state can be set to: 0x00: Coil Enabled 0x01: Coil Disabled 0x02: Coil Remains
Description |
Value |
---|---|
Index |
0x80E0 (Device) |
Subindex |
0x12 |
Datatype |
ENUM (UINT16) |
Min. Value |
|
Default |
Disable (1) |
Max. Value |
|
Unit |
|
Access / EtherCAT-State |
Rw |
PDO Mapping |
|
Revision |
All |
Enum Value |
Description |
---|---|
255 (0xFF) |
Error State |
2 (0x02) |
Remain |
1 (0x01) |
Disable |
0 (0x00) |
Enable |