60E1:03 RMS Current Error

The measured RMS current is greater than the setting "RMS Current Error Threshold"(8pp0:04). If the feature "RMS Current User Protection Enable"(8pp1:03) is active, the user protection has intervened and open the relay. While the feature "RMS Current User Protection Enable"(8pp1:03) is active and the diagnosis "RMS Current Error" is active, the relay remains open. To acknowledge the diagnosis "RMS Current Error" bit, the user has to generate a rising edge at the output bit "Reset"(6pp0:02). While the feature "RMS Current User Protection Enable"(8pp1:03) is disabled, the relay will remain in the actual output state. The diagnosis "RMS Current Error" is self-acknowledging. The user can define their own RMS current protection threshold by modifying the setting "RMS Current Error Threshold"(8pp0:04).

Description

Value

Index

0x60E1 (Device)

Subindex

0x03

Datatype

BOOL

Min. Value

 

Default

 

Max. Value

 

Unit

 

Access / EtherCAT-State

Ro

PDO Mapping

Transmit

Revision

All