2330, Earth leakage (motor-side)
The Iuvw sum Monitoring detected an Error.
| 
									 Diagnostic Code (Hex.)  | 
									 Diagnostic Code (Dez.)  | 
|---|---|
| 
									 2330  | 
									 9008  | 
| 
									 Class  | 
									 Type  | 
|---|---|
| 
									 Error  | 
									 Motor connection error  | 
| 
									 Standard Reaction  | 
									 Reset  | 
|---|---|
| 
									 Closed loop ramp  | 
									 Execute Reset-Command (Fault reset).  | 
| 
									 Possible Causes  | 
									 Solutions  | 
|---|---|
| 
									 Iuvw sum (0x3242/14) raised above the parameter Iuvw sum max (0x3243/07)  | 
									 Please check the Motor connection and validate the parameter value.  | 
Internal: 0x2330, Earth leakage (motor-side)