3181, Wrong mains type. Operating time counter: UU s., Entry counter: UU
The connected mains type (3Ph/AC, 1Ph/AC or DC) does not match with parametrized value of Mains type (0x8000:04).
|
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
|---|---|
|
3181 |
12673 |
|
Class |
Type |
|---|---|
|
Error |
Error |
|
Standard Reaction |
Reset |
|---|---|
|
PSM is not ready to operate |
Execute Reset-Command (Fault reset). |
|
Possible Causes |
Solutions |
|---|---|
|
Mains type (0x8000:04) is parametrized with wrong value. |
Check the parameter Mains type (0x8000:04) and correct its value. |
|
The mains supply is not connected right. |
Check the mains suppy and connected it right, Switch on the mains voltage again. |