P-x-0205 Power management status word

This parameter displayes the actual internal state of power management and can be used for diagnostic purposes.

Attributes

Name

Value

Datatype

binary

Data length in bit

16

Decimal point

0

Min. Value

0

Default

0

Max. Value

-

Unit

-

EtherCATState

-

Cyclic transfer

AT

Device parameter

Yes

Related to interface revision

changed from Rev. 210


P-x-0205 Power management status word 1:

Included in the “Parameter Set Switching” function group!

This IDN exists as P-0-0205 - P-7-0205.

Parameter structure

Bit

Description

0

Status Umains ok
0 = Umains is not ok
1 = Umains is ok

1

Umains Overvoltage
0 = No Umains overvoltage
1 = Umains overvoltage

2

Umains phase error
0 = No phase error
1 = Umains phase error

3

Status DC Link ok
0 = DClink is not ok
1 = DClink is ok

4

Ext. Umains relay
0 = Ready to switch off
1 = Ready to switch on

5

Status fan
0 = Fan is not active
1 = Fan is active

6

Status circuit
0 = Charging resistor is active
1 = Charging resistor is bypassed

7

Status internal chopper
0 = Internal chopper is not active
1 = Internal chopper is active

8

Status external chopper
0 = External chopper is not active
1 = External chopper is active

9

Status additional fan
0= Additional fan is not active
1= Additional fan is active

10

Extended power management (see P-0-0010, Bit 5)
0= disabled (from Rev. 210)
1= enabled (from Rev. 210)

11

Umains loss monitoring enabled
0= disabled (from Rev. 210)
1= enabled (from Rev. 210)

12

Umains loss (from Rev. 210)
0= Umains is not loss
1= Umains is loss

13--15

Reserved (from Rev. 210)