FA85, Feedback "Resolver": Excitation frequency not supported
Excitation frequency not supported.
|
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
|---|---|
|
FA85 |
64133 |
|
Class |
Type |
|---|---|
|
Error |
Parameter error |
|
Standard Reaction |
Reset |
|---|---|
|
The power stage is already switched off |
Execute Reset-Command (S-0-0099). |
|
Possible Causes |
Solutions |
|---|---|
|
You have parametrized an unsupported excitation frequency in IDN "P-0-0150". |
Only an 8 kHz excitation frequency is supported. |
![]() | Please consider this note! Only an 8 kHz excitation frequency is supported. |
|
Further Information |
|---|
|
AX5000_IDN-Description: "P-0-0150 -->Process channel-->Resolver-->Excitation frequency" |