FA84, Feedback "Resolver": Number of poles not supported.
The parametrized number of poles is not supported.
|
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
|---|---|
|
FA84 |
64132 |
|
Class |
Type |
|---|---|
|
Error |
Parameter error |
|
Standard Reaction |
Reset |
|---|---|
|
The power stage is already switched off |
Execute Reset-Command (S-0-0099). |
|
Possible Causes |
Solutions |
|---|---|
|
You have parametrized an unsupported number of poles. |
Please check the parametrization of IDN "P-0-0150". |
![]() | Please consider this note! Only resolvers with 2, 4, 6 and 8 poles are supported. |
|
Further Information |
|---|
|
AX5000_IDN-Description: "P-0-0150 -->Process channel-->Resolver-->Number of poles" |