F879, Feedback "AX572x": Supply voltage
Error in the setting of the controlled supply voltage (Sense)
|
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
|---|---|
|
F879 |
63609 |
|
Class |
Type |
|---|---|
|
Error |
Runtime error |
|
Standard Reaction |
Reset |
|---|---|
|
Open loop ramp |
Execute Reset-Command (S-0-0099). |
|
Possible Causes |
Solutions |
|---|---|
|
Feedback cable is defective. |
Check the feedback cable |
|
Plug connection of the feedback cable defective. |
Check the plug connection of the feedback cable. |
|
No Sense cores exist. |
Check the feedback cable or parameterize the feedback supply voltage to "unregulated" voltage. |
|
Further Information |
|---|
|
AX5000_IDN-Description: "P-0-0150" |