F73F, Feedback "general": Feedback id has been incorrectly parametrized
The internal ID parametrized in the feedback system does not correspond to the ID entered in the IDN "P-0-0150" or "P-0-0180".
|
Diagnostic Code (Hex.) |
Diagnostic Code (Dez.) |
|---|---|
|
F73F |
63295 |
|
Class |
Type |
|---|---|
|
Error |
Parameter error |
|
Standard Reaction |
Reset |
|---|---|
|
The power stage is already switched off |
Execute Reset-Command (S-0-0099). |
|
Possible Causes |
Solutions |
|---|---|
|
You have selected an incorrect feedback system. |
Compare the selected feedback system with the actually existing one. |
|
The feedback database was incorrectly parametrized. |
Call our support dept. and replace the feedback database. |
|
During the motor replacement a motor with different feedback was connected. |
Please correct the feedback-parameterization. |
|
Further Information |
|---|
|
AX5000_IDN-Description: "P-0-0150-->Parameter channel-->Identifier" or "P-0-0180-->Parameter channel-->Identifier" |