F342, Position offset: Offset can't be activated. Modulo calculation is active.
Position offset: Offset can't be activated. Modulo calculation is active.
| 
                   Diagnostic Code (Hex.)  | 
                   Diagnostic Code (Dez.)  | 
|---|---|
| 
                   F342  | 
                   62274  | 
| 
                   Class  | 
                   Type  | 
|---|---|
| 
                   Error  | 
                   Runtime error  | 
| 
                   Standard Reaction  | 
                   Reset  | 
|---|---|
| 
                   Nc handling  | 
                   Execute Reset-Command (S-0-0099).  | 
| 
                   Possible Causes  | 
                   Solutions  | 
|---|---|
| 
                   The position offset can't be activated because the modulo calculation is enabled.  | 
                   Activate the position offset before enabling the modulo calculation.  | 
| 
                   The position offset can't be activated because the modulo calculation is enabled.  | 
                   Update the AX5000 firmware to a version 2.06 or higher.  |