F166, Process data mapping: MDT - S-0-0024
The process data mapping has failed due to incorrect parametrization.
| 
                   Diagnostic Code (Hex.)  | 
                   Diagnostic Code (Dez.)  | 
|---|---|
| 
                   F166  | 
                   61798  | 
| 
                   Class  | 
                   Type  | 
|---|---|
| 
                   Error  | 
                   Parameter error  | 
| 
                   Standard Reaction  | 
                   Reset  | 
|---|---|
| 
                   The power stage is already switched off  | 
                   Execute Reset-Command (S-0-0099).  | 
| 
                   Possible Causes  | 
                   Solutions  | 
|---|---|
| 
                   An IDN has been entered in the IDN "S-0-0024" that does not exist in the firmware you are using.  | 
                   Remove this IDN from "S-0-0024".  | 
| 
                   Further Information  | 
|---|
| 
                   AX5000_Operating-Instructions - Chapter "Commissioning-->Process data handling" and AX5000_IDN-Description: "S-0-0024"  |