FB_CXReadKBusError

FB_CXReadKBusError 1:

The function block enables further information to be read out about a K-bus error in order to obtain a more precise error image and to enable better diagnosis.

The prerequisite for this is that you use the K-bus terminals directly on your CX.

Example: If you are using the K-bus extension and the cable of the K-bus extension is disconnected, then you will see a K-bus interruption as nErrorCode = 4 and the position where the K-bus has been interrupted as nErrorArgument = Position.

Further information on possible K-bus errors using the CX7000 as an example:
https://infosys.beckhoff.com/content/1033/cx7000/9948355595.html?id=6787792405096234356

FB_CXReadKBusError 2: Inputs

Name

Type

Description

bEnable

BOOL

Link this variable to bit 0 of the K-bus state to activate the read process automatically in case of a K-bus error.

The K-bus State is a Word variable. To mask out bit 0 of your linked variables, you can use <VariableName>.0.

FB_CXReadKBusError 3: Outputs

Name

Type

Description

bBusy

BOOL

The function block is active and working.

bError

BOOL

The function block has an error.

nErrorID

UDINT

ADS error code

bKBusError

BOOL

The K-bus has an error. Further information is available at the outputs nKBusErrorCode and nKBusErrorArgument.

nKBusErrorCode

UINT

K-bus error code

nKBusErrorArgument

UINT

K-bus error argument

Once the error has been corrected, the K-bus can be restarted via the function block IOF_DeviceReset (from the PLC library Tc2_IoFunctions).

Development environment

Target platform

PLC libraries to include

TwinCAT v3.1.4024.22

CX (x86, x64, ARM)