FB_WriteCouplerRegs

FB_WriteCouplerRegs 1:

The function block FB_WriteCouplerRegs can be used for write access to the coupler's table registers and the registers of the intelligent terminals. The coupler itself is referred to as terminal 0 (null). All the other terminals in the terminal block, with the exception of passive terminals (such as power supply terminals), are counted in ascending sequence (beginning with 1). All registers or only a subrange (between nStartReg and nEndReg) can be written to. Several seconds are required to write all registers (0.255) of a coupler table. The register values to be written are located in the structure stCouplerTable. The structure is an array of high and low bytes. Each array element corresponds to a register value (e.g.: stCouplerTable[ 5 ] == Register 5).

FB_WriteCouplerRegs 2: Inputs

VAR_INPUT
    stState         : PLCINTFSTRUCT;
    nTerminal       : BYTE := TERM_COUPLER;
    nTable          : BYTE;
    nStartReg       : BYTE;
    nEndReg         : BYTE;
    bExecute        : BOOL;
    stCouplerTable  : ST_CouplerTable;
    tTimeout        : TIME;
END_VAR

Name

Type

Description

stState

PLCINTFSTRUCT

Status word of the 2-byte PLC interface.

nTerminal

BYTE

Terminal number whose table register is to be accessed. The coupler has terminal number null. Passive terminals are not to be counted.

nTable

BYTE

Table number whose register values are to be read. Intelligent terminals only have one table for each terminal channel. A 4-channel terminal has the following table numbers: 0-3. However, an intelligent terminal only has a maximum of 64 register values per terminal channel.

nStartReg

BYTE

The number of the first register to be written.

nEndReg

BYTE

The number of the last register to be written.

bExecute

BOOL

The function block is enabled by a positive edge at this input.

stCouplerTable

 

ST_CouplerTable

Array of the register values to be written.

tTimeout

TIME

Specifies the time-out period that must not be exceeded when the function is executed.

FB_WriteCouplerRegs 3: Outputs

VAR_OUTPUT
    stCtrl   : PLCINTFSTRUCT;
    bBusy    : BOOL;
    bError   : BOOL;
    nErrId   : UDINT;
END_VAR

Name

Type

Description

stCtrl

PLCINTFSTRUCT

Control word of the 2-byte PLC interface.

bBusy

BOOL

When the function block is activated, this output is set and remains set until the function is completed.

bError

BOOL

If an error occurs during the execution of the function, this output is set after the bBusy output has been reset.

nErrId

UDINT

Supplies the error number when the bError output is set.

Error number

Error description

0

No error

0x100

Error at initialisation of the communication via the 2 byte PLC interface

0x200

Error during communication

0x300

Timeout-Error. The permitted execution time was exceeded

0x400

Wrong parameter value at register number

0x500

Wrong parameter value at table number

Requirements

Development environment

Target system type

PLC libraries to include (category group)

TwinCAT v3.1.0

PC or CX (x86, x64, ARM)

Tc2_Coupler (IO)