Output circuit breakers

Standard miniature circuit breakers (MCBs) are commonly used for AC supply systems but can also be used in DC branches if specified.

Such MCBs are designed to protect wires and circuits. When the ampere rating and characteristics of the MCB are matched to the wire size used, the wiring is considered thermally safe whether the MCB opens or not.

To avoid voltage dips and undervoltage situations in adjacent DC branches fed by the same source, fast (magnetic) tripping of the MCB is desirable. For example, a fast trip within 10ms avoids a shutdown and restart of the PLC. For this purpose, power supplies with high current reserves and large output capacitors are advantageous. In addition, the impedance of the faulty circuit must be sufficiently small so that the current can actually flow. The best current reserves of a power supply are of no help if Ohm's law does not allow the current to flow.

The following table provides typical test results showing which MCBs magnetically trip as a function of wire size and length. The lengths given correspond to the total length, which is the sum of the outgoing (+) and return (-) wire. The tests were performed without additional load.

Output circuit breakers 1:
Test circuit for maximum wire length

Test results for maximum wire length:

 

0.75mm2

1.0mm2

1.5mm2

2.5mm2

C-2A

23m

32m

43m

62m

C-3A

14m

18m

26m

39m

C-4A

8m

9m

14m

18m

C-6A

2m

2m

4m

6m

C-8A

0m

1m

1m

1m

 

0.75mm2

1.0mm2

1.5mm2

2.5mm2

B-6A

11m

13m

21m

29m

B-10A

2m

2m

4m

4m

B-13A

1m

1m

1m

2m