EMC

The EMC behavior of the device is designed for applications in industrial environments as well as residential, commercial or small business environments.

The device was tested according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.

This device complies with FCC Part 15.

Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must be able to deal with any interference received, including interference that may cause undesired operation.

EMC interference immunity

 

Fast transients (burst)

EN 61000-4-2

Contact discharge, 8 kV, criterion A

Air discharge, 15 kV, criterion A

EMC interference emission

 

Conducted interference emission, input lines

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

Limit values for DC power supply connections according to EN 61000-6-3 fulfilled

Conducted interference emission, output lines

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

Limit values for DC power supply connections according to EN 61000-6-3 fulfilled

Interference emission

EN 55011, EN 55022

Class B

Switching frequencies

Converter for auxiliary supply voltage

55 to 180 kHz

The frequency depends on the input voltage