Dielectric strength

The output voltage is earth-free and has no ohmic connection to earth. Type and factory tests are carried out by the manufacturer. Field tests can be performed in the field using suitable test equipment that ramps up the voltage with a slow ramp (2 s rising and 2 s falling). Before performing the test, connect all phase connections and all output poles. During the test set the cut-off current to the value in the table below.

Dielectric strength 1:
Dielectric strength

*) When checking the input to DC-OK, make sure that the maximum voltage between DC-OK and the output is not exceeded (column D). We recommend connecting the DC-OK pins and the output pins when performing the test.

 

A

B

C

D

Type test

60 s

2500 Vac

3000 Vac

500 Vac

500 Vac

Component test

5 s

2500 Vac

2500 Vac

500 Vac

500 Vac

Field test

5 s

2000 Vac

2000 Vac

500 Vac

500 Vac

Setting the cut-off current

> 10 mA

> 10 mA

> 40 mA

> 1 mA

To meet the PELV requirements according to EN 60204-1 section 6.4.1, we recommend that either the positive pole, the negative pole or any other part of the output circuit is connected to the protective earthing system. This helps to avoid situations where a load starts unexpectedly or cannot be disconnected if an unnoticed earth leakage occurs.