Output

Output

Output voltage

Nom.

DC 24 V

 

Adjustment range

Min.

24 - 28 Vdc

Guaranteed value

Max.

30 Vdc

This is the maximum output voltage that can occur in the end position of the potentiometer in clockwise direction due to tolerances. It is not a guaranteed value that can be achieved. A typical value is 28.5 V.

Factory settings

Typ.

24.1 Vdc

±0.2%, at full load (cold device), in "Single Use" mode

Typ.

24.1 Vdc

±0.2%, at full load (cold device), in "Parallel Use" mode

Typ.

25.1 Vdc

At idle, cold device, in "Parallel Use" mode

Line regulation

Max.

10 mV

3 x 323 - 576 Vac

Load regulation

Max.

50 mV

In "Single Use" mode: between 0 and 40 A, static value, see Fig. Output voltage over output current typ. in "Single Use" mode

Typ.

1000 mV

In "Parallel Use" mode: between 0 and 40 A, static value, see Fig. Output voltage over output current typ. in "Parallel Use" mode

Residual ripple and ripple voltage

Max.

100 mVPP

Bandwidth 20 Hz to 20 MHz, 50 ohm

Output current -
continuous

Nom.

40 A

At 24 V, see Fig. Output voltage over output current typ. in "Single Use" mode; output voltage over output current typ. in "Parallel Use" mode

Nom.

34.3 A

At 28 V, see Fig. Output voltage over output current typ. in "Single Use" mode; output voltage over output current typ. in "Parallel Use" mode

Output current -
Extra power up to 4 s1)

Nom.

60 A

At 24 V, see Fig. Output voltage over output current typ. in "Single Use" mode; output voltage over output current typ. in "Parallel Use" mode and Fig. Dynamic overcurrent capability, typ. < 10 ms; Dynamic overcurrent capability, typ. < 25 ms

 

Nom.

51.5 A

At 28 V, see Fig. Output voltage over output current typ. in "Single Use" mode; output voltage over output current typ. in "Parallel Use" mode and Fig. Dynamic overcurrent capability, typ. < 10 ms; Dynamic overcurrent capability, typ. < 25 ms

 

Output current

Typ.

110 A

up to 25 ms, output voltage remains above 20 V, see Fig. Dynamic overcurrent capacity, typ. < 10 ms; Dynamic overcurrent capability, typ. < 25 ms
This peak current is available once per second.

for further peak current measurements see chapter Peak current capability

Output power -
continuous

Nom.

960 W

At 24 - 28 V

Output power -
Extra Power 4 s1)

Nom.

1440 W

At 24 - 28 V

Extra power time
(bonus time)

Typ.

4 s

Time until the output voltage drops, see Fig. Bonus time over output power

Recovery time

Typ.

7 s

Overload-free time until the power manager is reset, see Fig. Extra power recovery time

Overload behavior

 

Continuous current

see Fig. Output voltage over output current, typ. in "Single Use" mode

Short-circuit current2)

Min.

40 A

Continuous, load impedance 25 mOhm, see Fig. Output voltage over output current, typ. in "Single Use" mode

Max.

44 A

Continuous, load impedance 25 mOhm, see Fig. Output voltage over output current, typ. in "Single Use" mode

Min.

60 A

Short term for 4 s, load impedance 25 mOhm, see Fig. Output voltage over output current, typ. in "Single Use" mode

Max.

68 A

Short term for 4 s, load impedance 25 mOhm, see Fig. Output voltage over output current, typ. in "Single Use" mode

Typ.

46 A

Continuous, load impedance < 10 mOhm

max

51 A

Continuous, load impedance < 10 mOhm

Output capacity

Typ.

10,200 μF

Included in the power supply

1) Extra power
The power supply is designed to support loads with higher short-term power requirements without damage or shutdown.
The short-time duration/bonus time is controlled in hardware by an output power manager.
Extra power is available repeatedly. Detailed information can be found in the chapter on Repeated pulse load.
If the power supply is subjected to extra power for longer than shown in the bonus time diagram (see Fig. Bonus time over output power), the maximum output power is automatically reduced to 960 W.

2) The discharge current of the output capacitors is not included.

Output 1:
Output voltage over output current typ. in "Single Use" mode; output voltage over output current typ. in "Parallel Use" mode,
Output 2:
Dynamic overcurrent capability, typ. < 10 ms; Dynamic overcurrent capability, typ. < 25 ms
Output 3:
Bonus time over output power; Extra power recovery time

Extra power is available as soon as the power is turned on and after an output short-circuit or output overload.

Output 4:
Extra power after switching on; extra power after short circuit or overload