AC input

AC input

AC input

Nom.

AC 100-240V

Suitable for TN, TT and IT networks

AC input range

Min.

85-264Vac

Continuous operation

Min.

264-300Vac

For up to 500ms max.

Permissible voltage L or N to earth

Max.

300Vac

Continuous according to IEC 60664-1

Input frequency

Nom.

50-60Hz

±6%

Turn-on voltage

Typ.

82Vac

Static, see Fig. Input voltage range; switch-on behavior definitions

Shut-down voltage

Typ.

72Vac

Static, see Fig. Input voltage range; switch-on behavior definitions

AC input

 

AC 100V

AC120V

AC230V

 

Input current

Typ.

5.15A

4.26A

2.23A

At 24 V, 20 A, see Fig. Input current over output current; power factor over output current

Power factor*)

 

Typ.

0.996

0.996

0.980

At 24 V, 20 A, see Fig. Input current over output current; power factor over output current

Peak factor**)

Typ.

1.65

1.63

1.63

At 24V, 20A

Start-up delay

Typ.

450ms

450ms

450ms

See Fig. Input voltage range; switch-on behavior definitions

Rise time

Typ.

145ms

145ms

145ms

At 24 V, 20 A constant current load, 0 mF load capacity, see Fig. Input voltage range; switch-on behavior definitions

Typ.

160ms

160ms

160ms

At 24 V, 20 A constant current load, 20 mF load capacity, see Fig. Input voltage range; switch-on behavior definitions

Turn-on overshoot

Max.

200 mV

200 mV

200 mV

See Fig. Input voltage range; switch-on behavior definitions

*) The power factor is the ratio of real (or active) power to apparent power in an AC circuit.

**) The peak factor is the mathematical ratio of the peak value to the RMS value of the input current waveform.

AC input 1:
Input voltage range; switch-on behavior definitions
AC input 2:
Input current over output current; power factor over output current