Lifetime expectancy

The lifetime expectancy shown in the table indicates the minimum number of operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. The lifetime expectancy is stated in operating hours and is calculated according to the specifications of the capacitor manufacturer.

Please note: The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131,400h). Any number exceeding this value represents a calculated theoretical service life which can be used to compare devices.

 

AC 100V

AC 120V

AC 230V

 

Lifetime expectancy

39,000h

64,000h

102,000h

At 24V, 3.8A and +40°C

260,000h

292,000h

309,000h

At 24V, 1.9A and +40°C

91,000h

147,000h

287,000h

At 24V, 3.8A and +25°C

640,000h

720,000h

815,000h

At 24V, 1.9A and +25°C