Cabling between KL6581 and KL6583
Notice | |
Cabling instructions:
|
Meaning | KL6581 | KL6583 X1 or X2 |
---|---|---|
CAN + | 1 | CAN + |
CAN - | 5 | CAN - |
24 V DC | 2 or 6 | 24 V |
GND | 3 or 7 | GND |
Node address of KL6583
S3 is for setting the node address. Each address may only be used once in the line (valid addresses: 1...8).
Termination resistor
The termination resistor must be activated in the last module!
To do this, both DIP switches S1 and S2 must be set to ON.
Risk of confusion The number ‘1’ on the DIP switches is only for numbering: The ‘1’ does not mean ON! |