Register overview

These registers exist once for each channel

Address

Name

Default value

R/W

Storage medium

R0…R5

reserved

0x0000

R

 

R6

Diagnostic register not used

0x0000

R

 

R7

Command register - not used

0x0000

R

 

R8

Terminal type

5001

R

ROM

R9

Software version number

0x????

R

ROM

R10

Multiplex shift register

0x0218

R

ROM

R11

Signal channels

0x0128

R

ROM

R12

Minimum data length

0x00A8

R

ROM

R13

Data structure

0x0000

R

ROM

R14

reserved

0x0000

R

 

R15

Alignment register

variable

R/W

RAM

R16

Hardware version number

0x????

R/W

SEEROM

R17…R30

reserved

0x0000

R/W

SEEROM

R31

Code word register

variable

R/W

RAM

R32

Feature register

0x0007

R/W

SEEROM

R33

Baud rate

0x0002

R/W

SEEROM

R34

Data length

0x0018

R/W

SEEROM

R35

Variable frame length*

0x0000

R/W

SEEROM

R36…R47

reserved

0x0000

R/W

SEEROM

*) from hardware version 08 and firmware version 4A