Contact assignment and LEDs

WARNING

Risk of injury through electric shock and damage to the device!

Bring the Bus Terminals system into a safe, de-energized state before starting mounting, disassembly or wiring of the Bus Terminals!

Contact assignment and LEDs 1:
KL5001 - Connection and LEDs

KL5001/KS5001 - Contact assignment

Terminal point

No.

Comment

D+

1

SSI data input D+

+24 V

2

+24 V (internally connected to terminal point 6 and positive power contact)

0 V

3

0 V (internally connected to terminal point 7 and negative power contact)

Cl+

4

Clock output CL+

D-

5

SSI data input D-

+24 V

6

+24 V (internally connected to terminal point 2 and positive power contact)

0 V

7

0 V (internally connected to terminal point 3 and negative power contact)

Cl-

8

Clock output CL-

KL5001/KS5001 - LED display

LED

Color

Description

Run1 LED

green

On:

Normal operation

Off:

Watchdog timer overflow has occurred. If no process data is transmitted to the bus coupler for 100 ms, the green LED goes out.