Settings
The dialog mask for parameterizing the KL4414 or KS4424 can be found under Settings.
Operation mode
- User scaling active (R32.0)
You can activate user scaling here (default: disabled).
- Manufacturer scaling active (R32.1)
You can deactivate manufacturer scaling here (default: enabled).
- Watchdog timer active (R32.2)
You can deactivate the watchdog timer here (default: enabled).
- Signed amount representation (R32.3)
Here you can enable the signed amount representation (default: disabled).
- Signed representation active (R32.5)
Here you can enable the signed representation (default: disabled).
- User switch-on value active (R32.8)
Here you can enable the user switch-on value (default: disabled).
Register data
- User offset (R33)
Here you can specify the user offset (default: 0).
- User gain (R34)
Here you can specify the user gain (default: 256).
- User switch-on value (R35)
Here you can specify the user switch-on value (default: 0).