KL4112 - Dual Channel Analog Output Terminal, 0 to 20 mA, 16 Bit

Register overview

 

These registers exist once for each channel

Address
Name
Default value
R/W
Storage medium
R0…R4
reserved
0x0000
R
RAM
Raw DAC value
variable
R
 
R6
Diagnostic register
0x0000
R
RAM
R7
Command register
0x0000
R
 
Terminal type
4112
R
ROM
Software version number
0x????
R
ROM
Multiplex shift register
0x0218
R
ROM
Signal channels
0x0218
R
ROM
Minimum data length
0x9800
R
ROM
Data structure
0x0000
R
ROM
R14
reserved
0x0000
R
 
Alignment register
variable
R/W
RAM
Hardware version number
0x????
R/W
SEEROM
Hardware compensation: Offset
specific
R/W
SEEROM
Hardware compensation: Gain
specific
R/W
SEEROM
Manufacturer scaling: Offset
0x0000
R/W
SEEROM
Manufacturer scaling: Gain
0x0000
R/W
SEEROM
R22…R30
reserved
0x0000
R/W
SEEROM
Code word register
variable
R/W
RAM
Feature register
0x0020
R/W
SEEROM
User scaling: Offset
0x0000
R/W
SEEROM
User scaling: Gain
0x0100
R/W
SEEROM
User switch-on value
0x0000
R/W
SEEROM
R36…R63
reserved
0x0000
R/W