Register overview

The following registers are used to parameterize the KL3404, KL3408, KL3464 and KL3468. Each signal channel of the analog terminal has one register that can be read or written to with the aid of control, status and data bytes via register communication.

Register no.

Comment

Default value

R/W

Memory

R0

Raw value of the A/D converter (XR)

-

-

R

RAM

R1

reserved

-

 

-

-

...

...

...

...

...

...

R5

reserved

-

-

-

-

R6

Diagnostic register

-

-

R

RAM

R7

Command register

0x0000

0dec

R/W

RAM

R8

Terminal type

KL3404:

0x0D4C

3404dec

R

ROM

KL3408:

0x0D50

3408dec

KL3464:

0x0D88

3464dec

KL3468:

0x0D8C

3468dec

R9

Firmware version

e.g. 0x3141

e.g. 1AASCII

R

ROM

R10

Data length (multiplex shift register)

0x0230

560dec

R

ROM

R11

Signal channels

0x0418

1048dec

R

ROM

R12

Minimum data length

0x0098

152dec

R

ROM

R13

Data structure (data type register)

0x0004

4dec

R

ROM

R14

reserved

-

-

-

-

R15

Alignment register

e.g. 0x7F80

e.g. 32640dec

R/W

RAM

R16

Hardware version number

e.g. 0x0000

e.g. 0dec

R/W

SEEPROM

R17

Hardware compensation: Offset (Ba)

0x0000

0dec

R/W

SEEPROM

R18

Hardware compensation:
Gain (Aa)

KL3404:

approx. 0x135A

approx. 4954dec

R/W

SEEPROM

KL3408:

KL3464:

approx. 0x13A6

approx. 5030dec

KL3468:

R19

Manufacturer scaling: Offset (Bh)

0x0000

0dec

R/W

SEEPROM

R20

Manufacturer scaling: Gain (Ah)

typ. 0x2000

typ. 8192dec

R/W

SEEPROM

R21

Overrange limit

KL3404:

0x07FF

2047dec

R/W

SEEPROM

KL3408:

KL3464:

0x0FFF

4095dec

R/W

SEEPROM

KL3468:

R22

Under range limit

KL3404:

0xF800

63488dec

R/W

SEEPROM

KL3408:

KL3464:

0x0000

0dec

R/W

SEEPROM

KL3468:

R23

reserved

-

-

-

-

...

...

...

...

...

...

R30

reserved

-

-

-

-

R31

Code word register

0x0000

0dec

R/W

RAM

R32

Feature register

0x0906

2310dec

R/W

SEEPROM

R33

User scaling: Offset (Bw) *

0x0000

0dec

R/W

SEEPROM

R34

User scaling: Gain (Aw)

0x0400

1024dec

R/W

SEEPROM

R35

Threshold 1 in (Y2)

0x0000

0dec

R/W

SEEPROM

R36

Threshold 2 in (Y2)

0x0000

0dec

R/W

SEEPROM

R37

Cut-off frequency of the digital IIR filter

0x0100

256dec

R/W

SEEPROM

R38

reserved

-

-

-

-

...

reserved

...

...

...

...

R63

reserved

-

-

-

-

*) Not supported by KL3404, KL3408, KL3464 and KL3468.