Mapping

Each Bus Terminal is mapped in the Bus Coupler. In the delivery state, this mapping occurs with the default settings of the Bus Coupler for this terminal. The default setting can be changed with the KS2000 configuration software or with a master configuration software (e.g. TwinCAT System Manager or ComProfibus).

If the terminals are complexly evaluated, they occupy memory space in the input and output process image.

The following tables provide information about the terminal mapping, depending on the conditions set in the Bus Coupler.

Default mapping for:
Lightbus, EtherCAT, Ethernet and Bus Terminal Controller (BCxxxx, BXxxxx)

Conditions

Word offset

High byte

Low byte

Complex evaluation: yes

Motorola format: no

Word alignment: yes

0

reserved

Ch0 CB/SB

1

Ch0 D1

Ch0 D0

2

r reserved

Ch1 CB/SB

3

Ch1 D1

Ch1 D0

Conditions

Word offset

High byte

Low byte

Complex evaluation: yes

Motorola format: yes

Word alignment: yes

0

reserved

Ch0 CB/SB

1

Ch0 D0

Ch0 D1

2

reserved

Ch1 CB/SB

3

Ch1 D0

Ch1 D1

Key

Default mapping for:
PROFIBUS, Interbus

Conditions

Word offset

High byte

Low byte

Complex evaluation: no

Motorola format: yes

Word alignment: don't care

0

Ch0 D0

Ch0 D1

1

Ch1 D0

Ch1 D1

2

Ch2 D0

Ch2 D1

3

Ch3 D0

Ch3 D1

Conditions

Word offset

High byte

Low byte

Complex evaluation: yes

Motorola format: no

Word alignment: no

0

Ch0 D0

Ch0 CB/SB

1

Ch1 CB/SB

Ch0 D1

2

Ch1 D1

Ch1 D0

3

Ch2 D0

Ch2 CB/SB

4

Ch3 CB/SB

Ch2 D1

5

Ch3 D1

Ch3 D0

Conditions

Word offset

High byte

Low byte

Complex evaluation: yes

Motorola format: yes

Word alignment: no

0

Ch0 D1

Ch0 CB/SB

1

Ch1 CB/SB

Ch0 D0

2

Ch1 D0

Ch1 D1

3

Ch2 D1

Ch2 CB/SB

4

Ch3 CB/SB

Ch2 D0

5

Ch3 D0

Ch3 D1

Default mapping for:
CANopen, CANCAL, DeviceNet, ControlNet, Modbus, RS232, RS485

Conditions

Word offset

High byte

Low byte

Complex evaluation: no

Motorola format: no

Word alignment: don't care

0

Ch0 D1

Ch0 D0

1

Ch1 D1

Ch1 D0

2

Ch2 D1

Ch2 D0

3

Ch3 D1

Ch3 D0