Process image

The terminals KL3132, KL3162, KL3142, KL3152 KL3172 and KL3148 are represented in the process image with a maximum of 6 bytes of input data and 6 bytes of output data. These are organized as follows:

Format

Input data

Output data

Byte

SB1

CB1

Word

DataIN1

DataOUT1

Byte

SB2

CB2

Word

DataIN2

DataOUT2

Key

SB n: Status byte for channel n
CB n: Control byte for channel n

DataIN n: Input data word channel n
DataOUT n: Output data word channel n

Representation of the analog values

The analog input values are represented by the terminals as follows:

KL3132-0000

Voltage

Decimal

Hexadecimal

-10 V

-32768

0x8000

+10 V

+32767

0x7FFF

KL3142-0000

Current

Decimal

Hexadecimal

0 mA

0

0x0000

20 mA

65535

0xFFFF

KL3152-0000

Current

Decimal

Hexadecimal

4 mA

0

0x0000

20 mA

65535

0xFFFF

KL3162-0000

Voltage

Decimal

Hexadecimal

0 V

0

0x0000

10 V

65535

0xFFFF

KL3172-0000

Voltage

Decimal

Hexadecimal

0 V

0

0x0000

2 V

65535

0xFFFF

KL3172-0500

Voltage

Decimal

Hexadecimal

0 V

0

0x0000

500 mV

65535

0xFFFF

KL3172-1000

Voltage

Decimal

Hexadecimal

0 V

0

0x0000

1 V

65535

0xFFFF

KL3182-0000

Voltage

Decimal

Hexadecimal

-2 V

-32768

0x8000

+2 V

+32767

0x7FFF